In order to promote public education and public safety, equal justice for all, a better informed citizenry, the rule of law, world trade and world peace, this legal document is hereby made available on a noncommercial basis, as it is the right of all humans to know and speak the laws that govern them.
EUROPEAN STANDARD
NORME EUROPÉENNE
EUROPӒISCHE NORM
EN 1992-1-2
December 2004
ICS 13.220.50; 91.010.30; 91.080.40
Supersedes ENV 1992-1-2:1995
Incorporating corrigendum July 2008
English version
Eurocode 2: Calcul des structures en béton - Partie 1-2: Règles générales - Calcul du comportement au feu | Eurocode 2: Planung von Stahlbeton- und Spannbetontragwerken - Teil 1-2: Allgemeine Regeln -Tragwerksbemessung für den Brandfall |
This European Standard was approved by CEN on 8 July 2004.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2004 CEN
All rights of exploitation in any form and by any means reserved worldwide for CEN national Members.
Ref. No. EN 1992-1-2:2004: E
11 | General | |||
1.1 | Scope | |||
1.1.1 | Scope of Eurocode 2 | |||
1.1.2 | Scope of Part 1 -2 of Eurocode 2 | |||
1.2 | Normative references | |||
1.3 | Assumptions | |||
1.4 | Distinctions between principles and application rules | |||
1.5 | Definitions | |||
1.6 | Symbols | |||
1.6.1 | Supplementary symbols to EN 1992-1-1 | |||
1.6.2 | Supplementary subscripts to EN 1992-1-1 | |||
2 | Basis of design | |||
2.1 | Requirements | |||
2.1.1 | General | |||
2.1.2 | Nominal fire exposure | |||
2.1.3 | Parametric fire exposure | |||
2.2 | Actions | |||
2.3 | Design values of material properties | |||
2.4 | Verification methods | |||
2.4.1 | General | |||
2.4.2 | Member analysis | |||
2.4.3 | Analysis of part of the structure | |||
2.4.4 | Global structural analysis | |||
3 | Material properties | |||
3.1 | General | |||
3.2 | Strength and deformation properties at elevated temperatures | |||
3.2.1 | General | |||
3.2.2 | Concrete | |||
3.2.2.1 | Concrete under compression | |||
3.2.2.2 | Tensile strength | |||
3.2.3 | Reinforcing steel | |||
3.2.4 | Prestressing steel | |||
3.3 | Thermal and physical properties of concrete with siliceous and calcareous aggregates | |||
3.3.1 | Thermal elongation | |||
3.3.2 | Specific heat | |||
3.3.3 | Thermal conductivity | |||
3.4 | Thermal elongation of reinforcing and prestressing steel | |||
4 | Design procedures | |||
4.1 | General | |||
4.2 | Simplified calculation method | |||
4.2.1 | General | |||
4.2.2 | Temperature profiles | |||
4.2.3 | Reduced cross-section | |||
4.2.4 | Strength reduction | |||
4.2.4.1 | General2 | |||
4.2.4.2 | Concrete | |||
4.2.4.3 | Steel | |||
4.3 | Advanced calculation methods | |||
4.3.1 | General | |||
4.3.2 | Thermal response | |||
4.3.3 | Mechanical response | |||
4.3.4 | Validation of advanced calculation models | |||
4.4 | Shear, torsion and anchorage | |||
4.5 | Spalling | |||
4.5.1 | Explosive spalling | |||
4.5.2 | Falling off of concrete | |||
4.6 | Joints | |||
4.7 | Protective layers | |||
5 | Tabulated data | |||
5.1 | Scope | |||
5.2 | General design rules | |||
5.3 | Columns | |||
5.3.1 | General | |||
Method A | ||||
5.3.3 | Method B |
|||
5.4 | Walls | |||
5.4.1 | Non load bearing compartmentation walls |
|||
5.4.2 | Load-bearing solid walls | |||
5.4.3 | Firewalls | |||
5.5 | Tensile members | |||
5.6 | Beams | |||
5.6.1 | General | |||
5.6.2 | Simply supported beams | |||
5.6.3 | Continuous beams | |||
5.6.4 | Beams exposed on all sides | |||
5.7 | Slabs | |||
5.7.1 | General | |||
5.7.2 | Simply supported solid slabs | |||
5.7.3 | Continuous solid slabs | |||
5.7.4 | Flat slabs | |||
5.7.5 | Ribbed slabs | |||
6 | High strength concrete (HSC) | |||
6.1 | General | |||
6.2 | Spalling | |||
6.3 | Thermal properties | |||
6.4 | Structural design | |||
6.4.1 | Calculation of load-carrying capacity | |||
6.4.2 | Simplified calculation method | |||
6.4.2.1 | Columns and walls | |||
6.4.2.2 | Beams and slabs | |||
6.4.3 | Tabulated data |
A | Temperature profiles |
B | Simplified calculation methods |
C | Buckling of columns under fire conditions |
D | Calculation methods for shear, torsion and anchorage |
E | Simplified calculation method for beams and slabs |
This European Standard EN 1992-1-2 , “Design of concrete structures - Part 1-2 General rules -Structural fire design”, has been prepared by Technical Committee CEN/TC250 “Structural Eurocodes”, the Secretariat of which is held by BSI. CEN/TC250 is responsible for all Structural Eurocodes.
This European Standard shall be given the status of a National Standard, either by publication of an identical text or by endorsement, at the latest by June 2005, and conflicting National Standards shall be withdrawn at latest by March 2010.
This European standard supersedes ENV 1992-1-2: 1995.
According to the CEN-CENELEC Internal Regulations, the National Standard Organisations of the following countries are bound to implement these European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
In 1975, the Commission of the European Community decided on an action programme in the field of construction, based on article 95 of the Treaty. The objective of the programme was the elimination of technical obstacles to trade and the harmonisation of technical specifications.
Within this action programme, the Commission took the initiative to establish a set of harmonised technical rules for the design of construction works which, in a first stage, would serve as an alternative to the national rules in force in the Member States and, ultimately, would replace them.
For fifteen years, the Commission, with the help of a Steering Committee with Representatives of Member States, conducted the development of the Eurocodes programme, which led to the first generation of European codes in the 1980s.
In 1989, the Commission and the Member States of the EU and EFTA decided, on the basis of an agreement1 between the Commission and CEN, to transfer the preparation and the
1Agreement between the Commission of the European Communities and the European Committee for Standardisation (CEN) concerning the work on EUROCODES for the design of building and civil engineering works (BC/CEN/03/89).
4publication of the Eurocodes to the CEN through a series of Mandates, in order to provide them with a future status of European Standard (EN). This links de facto the Eurocodes with the provisions of all the Council’s Directives and/or Commission’s Decisions dealing with European standards (e.g. the Council Directive 89/106/EEC on construction products - CPD - and Council Directives 93/37/EEC, 92/50/EEC and 89/440/EEC on public works and services and equivalent EFTA Directives initiated in pursuit of setting up the internal market).
The Structural Eurocode programme comprises the following standards generally consisting ofa number of Parts:
EN 1990 | Eurocode: | Basis of Structural Design |
EN 1991 | Eurocode 1: | Actions on structures |
EN 1992 | Eurocode 2: | Design of concrete structures |
EN 1993 | Eurocode 3: | Design of steel structures |
EN 1994 | Eurocode 4: | Design of composite steel and concrete structures |
EN 1995 | Eurocode 5: | Design of timber structures |
EN 1996 | Eurocode 6: | Design of masonry structures |
EN 1997 | Eurocode 7: | Geotechnical design |
EN 1998 | Eurocode 8: | Design of structures for earthquake resistance |
EN 1999 | Eurocode 9: | Design of aluminium structures |
Eurocode standards recognise the responsibility of regulatory authorities in each Member State and have safeguarded their right to determine values related to regulatory safety matters at national level where these continue to vary from State to State.
The Member States of the EU and EFTA recognise that Eurocodes serve as reference documents for the following purposes:
The Eurocodes, as far as they concern the construction works themselves, have a direct relationship with the Interpretative Documents2 referred to in Article 12 of the CPD, although they are of a different nature from harmonised product standards3. Therefore, technical aspects arising from the Eurocodes work need to be adequately considered by CEN Technical
2 According to Art. 3.3 of the CPD, the essential requirements (ERs) shall be given concrete form in interpretative documents for the creation of the necessary links between the essential requirements and the mandates for harmonised ENs and ETAGs/ETAs.
3 According to Art. 12 of the CPD the interpretative documents shall:
Committees and/or EOTA Working Groups working on product standards with a view to achieving full compatibility of these technical specifications with the Eurocodes.
The Eurocode standards provide common structural design rules for everyday use for the design of whole structures and component products of both a traditional and an innovative nature. Unusual forms of construction or design conditions are not specifically covered and additional expert consideration will be required by the designer in such cases.
The National Standards implementing Eurocodes will comprise the full text of the Eurocode (including any annexes), as published by CEN, which may be preceded by a National title page and National foreword, and may be followed by a National Annex.
The National Annex may only contain information on those parameters which are left open in the Eurocode for national choice, known as Nationally Determined Parameters, to be used for the design of buildings and civil engineering works to be constructed in the country concerned, i.e. :
There is a need for consistency between the harmonised technical specifications for construction products and the technical rules for works4. Furthermore, all the information accompanying the CE Marking of the construction products which refer to Eurocodes should clearly mention which Nationally Determined Parameters have been taken into account.
EN 1992- 1-2 describes the Principles, requirements and rules for the structural design of buildings exposed to fire, including the following aspects.
EN 1992-1-2 is intended for clients (e.g. for the formulation of their specific requirements), designers, contractors and relevant authorities.
The general objectives of fire protection are to limit risks with respect to the individual and society, neighbouring property, and where required, environment or directly exposed property, in the case of fire.
4 see Art.3.3 and Art. 12 of the CPD, as well as clauses 4.2, 4.3.1, 4.3.2 and 5.2 of ID 1.
6Construction Products Directive 89/106/EEC gives the following essential requirement for the limitation of fire risks:
“The construction works must be designed and build in such a way, that in the event of an outbreak of fire
According to the Interpretative Document N° 2 “Safety in case of fire” the essential requirement may be observed by following various possibilities for fire safety strategies prevailing in the Member states like conventional fire scenarios (nominal fires) or “natural” (parametric) fire scenarios, including passive and/or active fire protection measures.
The fire parts of Structural Eurocodes deal with specific aspects of passive fire protection in terms of designing structures and parts thereof for adequate load bearing resistance and for limiting fire spread as relevant.
Required functions and levels of performance can be specified either in terms of nominal (standard) fire resistance rating, generally given in national fire regulations or by referring to fire safety engineering for assessing passive and active measures, see EN 1991-1-2.
Supplementary requirements concerning, for example:
- – the possible installation and maintenance of sprinkler systems,
- – conditions on occupancy of building or fire compartment,
- – the use of approved insulation and coating materials, including their maintenance,
are not given in this document, because they are subject to specification by the competent authority.
Numerical values for partial factors and other reliability elements are given as recommended values that provide an acceptable level of reliability. They have been selected assuming that an appropriate level of workmanship and of quality management applies.
A full analytical procedure for structural fire design would take into account the behaviour of the structural system at elevated temperatures, the potential heat exposure and the beneficial effects of active and passive fire protection systems, together with the uncertainties associated with these three features and the importance of the structure (consequences of failure).
At the present time it is possible to undertake a procedure for determining adequate performance which incorporates some, if not all, of these parameters and to demonstrate that the structure, or its components, will give adequate performance in a real building fire. However, where the procedure is based on a nominal (standard) fire the classification system, which call for specific periods of fire resistance, takes into account (though not explicitly), the features and uncertainties described above.
7Application of design procedures is illustrated in Figure 0.1. The prescriptive approach and the performance-based approach are identified. The prescriptive approach uses nominal fires to generate thermal actions. The performance-based approach, using fire safety engineering, refers to thermal actions based on physical and chemical parameters. Additional information for alternative methods in this standard is given in Table 0.1.
For design according to this part, EN 1991-1-2 is required for the determination of thermal and mechanical actions to the structure.
Where simple calculation models are not available, the Eurocode fire parts give design solutions in terms of tabulated data (based on tests or advanced calculation models), which may be used within the specified limits of validity.
It is expected, that design aids based on the calculation models given in EN 1992-1-2, will be prepared by interested external organisations.
The main text of EN 1992-1-2, together with informative Annexes A, B, C, D and E, includes most of the principal concepts and rules necessary for structural fire design of concrete structures.
This standard gives alternative procedures, values and recommendations for classes with notes indicating where national choices may have to be made. Therefore the National Standard implementing EN 1992-1-2 should have a National Annex containing the Eurocode all Nationally Determined Parameters to be used for the design of buildings, and where required and applicable, for civil engineering works to be constructed in the relevant country.
National choice is allowed in EN 1992-1-2 through clauses:
Figure 1 : Alternative design procedures
Tabulated data | Simplified calculation methods | Advanced calculation models | |
---|---|---|---|
Member analysis The member is considered as isolated. Indirect fire actions are not considered, except those resulting from thermal gradients |
YES
|
YES
|
YES, 4.3.1(1)P Only the principles are given |
Indirect fire actions within the subassembly are considered , |
NO | YES
|
YES 4.3.1(1)P Only the principles are given |
Global structural analysis Analysis of the entire structure. Indirect fire actions are considered throughout the structure | NO | NO | YES 4.3.1(1)P Only the principles are given |
The following normative documents contain provisions that, through reference in this text, constitute provisions of this European Standard. For dated references, subsequent amendments to, or revisions of, any of these publications do not apply. However, parties to agreements based on this European Standard are encouraged to investigate the possibility of applying the most recent editions of the normative documents indicated below. For undated references, the latest edition of the normative document referred to applies.
EN 1363-2: Fire resistance tests - Part 2: Alternatives and additional procedures;
EN 1990: Eurocode: Basis of structural design;
EN 1991-1-2: Eurocode 1 - Actions on structures - Part 1-2: General actions - Actions on structures exposed to fire;
EN 1992-1-1: Eurocode 2. Design of concrete structures - Part 1.1: General rules and rules for buildings
EN 10080: Steel for the reinforcement of concrete - Weldable reinforcing steel - General
EN 10138-2: Prestressing steels - Part 2: Wire
EN 10138-3: Prestressing steels - Part 3: Strand
EN 10138-4: Prestressing steels - Part 4: Bar
The general assumptions given in EN 1990 and EN 1992-1-1 apply.
For the purposes of this Part 1-2 of EN 1992, the definitions of EN 1990 and of EN 1991-1-2 apply with the additional definitions:
Critical temperature of reinforcement: The temperature of reinforcement at which failure of the member in fire situation (Criterion R) is expected to occur at a given steel stress level.
Fire wall: A wall separating two spaces (generally two buildings) that is designed for fire resistance and structural stability, and may include resistance to horizontal loading such that, in case of fire and failure of the structure on one side of the wall, fire spread beyond the wall is avoided.
11Maximum stress level: For a given temperature, the stress level at which the stress-strain relationship of steel is truncated to provide a yield plateau.
Part of structure: isolated part of an entire structure with appropriate support and boundary conditions.
Protective layers: Any material or combination of materials applied to a structural member for the purpose of increasing its fire resistance.
Reduced cross section: Cross section of the member in structure fire design used in the reduced cross section method. It is obtained by removing parts of the
cross section with assumed zero strength and stiffness.
Latin upper case letters
Ed,fi | design effect of actions in the fire situation |
Ed | design effect of actions for normal temperature design |
Rd,fi | design resistance in the fire situation; Rd,fi(t) at a given time t. |
R 30 or R 60,... fire resistance class for the load-bearing criterion for 30, or 60... minutes in standard fire exposure | |
E 30 or E 60,... fire resistance class for the integrity criterion for 30, or 60... minutes in standard fire exposure | |
I 30 or I 60,... fire resistance class for the insulation criterion for 30, or 60... minutes in standard fire exposure | |
T | temperature [K] (cf θ temperature [°C]); |
Xk | characteristic value of a strength or deformation property for normal temperature design |
Xd,fi | design strength or deformation property in the fire situation |
Latin upper case letters
a | axis distance of reinforcing or prestressing steel from the nearest exposed surface |
cc | specific heat of concrete [J/kgK] |
fck(θ) | characteristic value of compressive strength of concrete at temperature θ for a specified strain |
fck,t(θ) | characteristic value of tensile strength of concrete at temperature θ for a specified strain12 |
fpk(θ) | characteristic value of strength of prestressing steel at temperature θ for a specified strain |
fsk(θ) | characteristic strength of reinforcing steel at temperature θ for a specified strain |
k(θ)= Xk(θ)/Xk | reduction factor for a strength or deformation property dependent on the material temperature θ |
n = | N0Ed,fi /(0,7(Ac fcd + As fyd)) load level of a column at normal temperature conditions |
time in fire exposure (min) |
Latin upper case letters
γM,fi | partial safety factor for a material in fire design |
ηfi | = Ed,fi/Ed reduction factor for design load level in the fire situation |
μfi | = NEd,fi/NRd degree of utilisation in fire situation |
εc(θ) | thermal strain of concrete |
εp(θ) | thermal strain of prestressing steel |
εs(θ) | thermal strain of reinforcing steel |
εs,fi | strain of the reinforcing or prestressing steel at temperature θ |
λc | thermal conductivity of concrete [W/mK] |
λ0,fi | slenderness of the column under fire conditions |
σc,fi | compressive stress of concrete in fire situation |
σs,fi | steel stress in fire situation |
θ | temperature [°C] |
θcr | critical temperature [°C] |
Supplementary to EN 1992-1-1, the following subscripts are used:
fi | value relevant for the fire situation |
t | dependent on the time |
θ | dependent on the temperature |
Note l: See EN 1991-1-2 for the definitions.
Note 2: For concrete structures considered in this Part 1-2 thermal radiation criteria are not relevant.
Note: The values of ∆θ1 and ∆θ2 for use in a Country may be found in its National Annex. The recommended values are ∆θ1 = 200 K and ∆θ2 = 240 K.
Xd,fi = kθXk/γM,fi (2.1)
where
Xk | is the characteristic value of a strength or deformation property (generally fk or Ek) for normal temperature design to EN 1992-1-1; |
ke | is the reduction factor for a strength or deformation property (Xk,θ/Xk), dependent on the material temperature, see 3.2.; |
γM,fi | is the partial safety factor for the relevant material property, for the fire situation. |
Xd.fi = Xk,θ/γM,fi (2.2a)
Xd,fi = γM,fiXk,θ (2.2b)
where:
15Xk,θ | is the value of a material property in fire design, generally dependent on the material temperature, see section 3; |
γM,fi | is the partial safety factor for the relevant material property, for the fire situation. |
Note 1: The value of γM,fi for use in a Country may be found in its National Annex. The reconnrnended value is; For thermal properties of concrete and reinforcing and prestressing steel: γM,fi = 1,0
For mechanical properties of concrete and reinforcing and prestressing steel: γM,fi = 1,0
Note 2: If the recommended values are modified, the tabulated data may require modification.
Ed,fi ≤ Rd,t.fi (2.3)
where
Ed,fi | is the design effect of actions for the fire situation, determined in accordance with EN 1991-1-2, including effects of thermal expansions and deformations |
Rd,t,fi | is the corresponding design resistance in the fire situation. |
Note: For verifying standard fire resistance requirements, a member analysis is sufficient.
Ed,fi = ηfiEd (2.4)
Where
Ed | is the design value of the corresponding force or moment for normal temperature design, for a fundamental combination of actions (see EN 1990); |
ηft | is the reduction factor for the design load level for the fire situation. |
or for load combination (6.10a) and (6.10b) in EN 1990 as the smaller value given by the two following expressions:
where
Qk,1 | is the principal variable load; |
Gk | is the characteristic value of a permanent action; |
γG | is the partial factor for a permanent action; |
γQ,1 | is the partial factor for variable action 1; |
ψfi | is the combination factor for frequent or quasi-permanent values given either by ψ1,1 or ψ2,1, see EN 1991-1-2 |
ξ | is a reduction factor for unfavourable permanent action G |
Note 1: Regarding equation (2.5), examples of the variation of the reduction factor ηfi versus the load ratio Qk,i/Gk for Expression (2.4) and different values of the combination factor η1,1 are shown in Figure 2.1 with the following assumptions: γGA = 1,0, γG = 1,35 and γQ = 1,5. Expressions (2.5a) and (2.5b) give slightly higher values. Recommended values of partial factors are given in the relevant National Annexes of EN 1990.
Note 2: As a simplification a recommended value of ηfi = 0,7 may be used.
Figure 2.1 : Variation of the reduction factor γfi with the load ratio Qki/Gk
Alternative formulations of material laws may be applied, provided the solutions are within the range of experimental evidence.
Note: Material properties for lightweight aggregate concrete are not given in this Eurocode.
Concrete | Siliceous aggregates | Calcareous aggregates | ||||
temp.θ | fc,θ/fck | εc1,θ | εcu1,θ | fc,θ/fck | εc1,θ | εcu1,θ |
[°C] | [-] | [-] | [-] | [-] | [-] | [-] |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
20 | 1,00 | 0,0025 | 0,0200 | 1,00 | 0,0025 | 0,0200 |
100 | 1,00 | 0,0040 | 0,0225 | 1,00 | 0,0040 | 0,0225 |
200 | 0,95 | 0,0055 | 0,0250 | 0,97 | 0,0055 | 0,0250 |
300 | 0,85 | 0,0070 | 0,0275 | 0,91 | 0,0070 | 0,0275 |
400 | 0,75 | 0,0100 | 0,0300 | 0,85 | 0,0100 | 0,0300 |
500 | 0,60 | 0,0150 | 0,0325 | 0,74 | 0,0150 | 0,0325 |
600 | 0,45 | 0,0250 | 0,0350 | 0,60 | 0,0250 | 0,0350 |
700 | 0,30 | 0,0250 | 0,0375 | 0,43 | 0,0250 | 0,0375 |
800 | 0,15 | 0,0250 | 0,0400 | 0,27 | 0,0250 | 0,0400 |
900 | 0,08 | 0,0250 | 0,0425 | 0,15 | 0,0250 | 0,0425 |
1000 | 0,04 | 0,0250 | 0,0450 | 0,06 | 0,0250 | 0,0450 |
1100 | 0,01 | 0,0250 | 0,0475 | 0,02 | 0,0250 | 0,0475 |
1200 | 0,00 | − | − | 0,00 | − | − |
Figure 3.1: Mathematical model for stress-strain relationships of concrete under compression at elevated temperatures.
fck,t(θ) = Kc,t(θ)fck,t (3.1)
Kc,t(θ) = 1,0 | for 20 °C ≤ θ 100 °C |
Kc,t(θ) = 1,0 − 1,0 (θ − 100)/500 | for 100 °C < θ ≤ 600 °C |
Figure 3.2: Coefficient kc,t(θ) allowing for decrease of tensile strength (fck,t) of concrete at elevated temperatures
Figure 3.3: Mathematical model for stress-strain relationships of reinforcing and prestressing steel at elevated temperatures (notations for prestressing steel “p” instead of “s")
23Steel Temperature θ[°C] |
fsy,θ/fyk | fsp,θ/fyk | Es,θ/Es | |||
---|---|---|---|---|---|---|
hot rolled | cold worked | hot rolled | cold worked | hot rolled | cold worked | |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
20 | 1,00 | 1,00 | 1,00 | 1,00 | 1,00 | 1,00 |
100 | 1,00 | 1,00 | 1,00 | 0,96 | 1,00 | 1,00 |
200 | 1,00 | 1,00 | 0,81 | 0,92 | 0,90 | 0,87 |
300 | 1,00 | 1,00 | 0,61 | 0,81 | 0,80 | 0,72 |
400 | 1,00 | 0,94 | 0,42 | 0,63 | 0,70 | 0,56 |
500 | 0,78 | 0,67 | 0,36 | 0,44 | 0,60 | 0,40 |
600 | 0,47 | 0,40 | 0,18 | 0,26 | 0,31 | 0,24 |
700 | 0,23 | 0,12 | 0,07 | 0,08 | 0,13 | 0,08 |
800 | 0,11 | 0,11 | 0,05 | 0,06 | 0,09 | 0,06 |
900 | 0,06 | 0,08 | 0,04 | 0,05 | 0,07 | 0,05 |
1000 | 0,04 | 0,05 | 0,02 | 0,03 | 0,04 | 0,03 |
1100 | 0,02 | 0,03 | 0,01 | 0,02 | 0,02 | 0,02 |
1200 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 |
Steel Temperature θ[°C] |
fsy,θ/fyk hot rolled and cold worked |
fsp,θ/fyk hot rolled and cold worked |
Es,θ/Es hot rolled and cold worked |
---|---|---|---|
20 | 1,00 | 1,00 | 1,00 |
100 | 1,00 | 1,00 | 1,00 |
200 | 1,00 | 0,87 | 0,95 |
300 | 1,00 | 0,74 | 0,90 |
400 | 0,90 | 0,70 | 0,75 |
500 | 0,70 | 0,51 | 0,60 |
600 | 0,47 | 0,18 | 0,31 |
700 | 0,23 | 0,07 | 0,13 |
800 | 0,11 | 0,05 | 0,09 |
900 | 0,06 | 0,04 | 0,07 |
1000 | 0,04 | 0,02 | 0,04 |
1100 | 0,02 | 0,01 | 0,02 |
Note: The choice of Class N (Table 3.2a) or X (Table 3.2b) to be used in a Country may be found in its National Annex. Class N is generally recommended. Class X is recommended only when there is experimental evidence for these values.
24For Class A, β is given by Expression (3.2) (see Table 3.3):
Where the definitions and values for εud, εuk, fp0,1k, fpk and Ep at normal temperature are given in Section 3.3 of EN 1992-1-1.
For Class B, β is equal to 0,9 (see Table 3.3).
Note: The choice of Class A or Class B for use in a Country may be found in its National Annex.
Steel temp. θ[°C] |
fpy,θ/βfpk | fpy,θ/βfpk | Ep,θ/Ep | εpt,β[-] | εpu,β[-] | ||||
---|---|---|---|---|---|---|---|---|---|
cw | q & t | cw | q & t | cw | q & t | cw, q&t | cw, q&t | ||
Class A | Class B | ||||||||
1 | 2a | 2b | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
20 | 1,00 | 1,00 | 1,00 | 1,00 | 1,00 | 1,00 | 1,00 | 0,050 | 0,100 |
100 | 1,00 | 0,99 | 0,98 | 0,68 | 0,77 | 0,98 | 0,76 | 0,050 | 0,100 |
200 | 0,87 | 0,87 | 0,92 | 0,51 | 0,62 | 0,95 | 0,61 | 0,050 | 0,100 |
300 | 0,70 | 0,72 | 0,86 | 0,32 | 0,58 | 0,88 | 0,52 | 0,055 | 0,105 |
400 | 0,50 | 0,46 | 0,69 | 0,13 | 0,52 | 0,81 | 0,41 | 0,060 | 0,110 |
500 | 0,30 | 0,22 | 0,26 | 0,07 | 0,14 | 0,54 | 0,20 | 0,065 | 0,115 |
600 | 0,14 | 0,10 | 0,21 | 0,05 | 0,11 | 0,41 | 0,15 | 0,070 | 0,120 |
700 | 0,06 | 0,08 | 0,15 | 0,03 | 0,09 | 0,10 | 0,10 | 0,075 | 0,125 |
800 | 0,04 | 0,05 | 0,09 | 0,02 | 0,06 | 0,07 | 0,06 | 0,080 | 0,130 |
900 | 0,02 | 0,03 | 0,04 | 0,01 | 0,03 | 0,03 | 0,03 | 0,085 | 0,135 |
1000 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,090 | 0,140 |
1100 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,095 | 0,145 |
1200 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,00 | 0,100 | 0,150 |
Note: For intermediate values of temperature, linear interpolation may be used. |
Siliceous aggregates:
εc(θ) = −1,8 × 10−4 + 9 × 10−6 θ + 2,3 × 10−11 θ3 | for 20°C ≤ θ ≤ 700°C |
εc(θ) = 14 × 10−3 | for 700°C < θ ≤ 1200°C |
Calcareous aggregates:
εc(θ) = −1,2 × 10−4 + 6 × 10−6θ + 1,4 × 10−11 θ3 | for 20°C ≤ θ ≤ 805°C |
εc(θ) = 12 × 10−3 | for 805°C < θ ≤ 1200°C |
Where θ is the concrete temperature (°C).
Figure 3.5 Total thermal elongation of concrete
Siliceous and calcareous aggregates:
Cp(θ) = 900 (J/kg K) | 20°C ≤ θ ≤ 100°C |
Cp(θ) = 900 + (θ − 100)(J/kg K) | for 100°C < θ ≤ 200°C |
Cp(θ) = 1000 + (θ − 200)/2 (J/kg K) | for 200°C < θ ≤ 400°C |
Cp(θ) = 1100 (J/kg K) | for 400°C < θ ≤ 1200°C |
where θ is the concrete temperature (°C). cp(θ) (kJ /kg K) is illustrated in Figure 3.6a.
cp.peak = 900 J/kg K for moisture content of 0 % of concrete weight
cp.peak = 1470 J/kg K for moisture content of 1,5 % of concrete weight
cp.peak = 2020 J/kg K for moisture content of 3,0 % of concrete weight
And linear relationship between (115°C, cp.peak) and (200°C, 1000 J/kg K). For other moisture contents a linear interpolation is acceptable. The peaks of specific heat are illustrated in Figure 3.6a.
Figure 3.6: Specific heat and volumetric specific heat
27p(θ) = p(20°C) | for 20°C ≤ θ ≤ 115°C |
p(θ) = p(20°C)·(1 −0,02(0 − 115)/85) | for 115°C < θ ≤ 200°C |
p(θ) = p(20°C)·(0,98 · 0,03(0 − 200)/200) | for 200°C < θ ≤ 400°C |
p(θ) = p(20°C)·(0,95 − 0,07(0− 400)/800) | for 400°C < θ ≤ 1200°C |
Note 1: The value of thermal conductivity may be set by the National annex within the range defined by lower and upper limit.
Note 2: Annex A is compatible with the lower limit. The remaining clauses of this part 1-2 are independent of the choice of thermal conductivity. For high strength concrete, see 6.3.
λc = 2 − 0,2451 (θ/100) + 0,0107 (θ/100)2 W/m K | for 20°C ≤ θ≤ 1200°C |
where θ is the concrete temperature.
The lower limit of thermal conductivity λc of normal weight concrete may be determined from:
λc = 1,36 − 0,136 (θ/100) + 0,0057 (θ/100)2 W/m K | for 20°C ≤ θ≤ 1200°C |
where θ is the concrete temperature.
Reinforcing steel:
εs(θ) = −2,416 × 10−4 + 1,2×10−5 θ+ 0,4 × 10−8 θ2 | for 20°C ≤ θ ≤ 750°C |
εs(θ) = 11 × 10−3 | for 750°C < θ ≤ 860°C |
εs(θ) = −6,2 × 10−3 + 2 × 10−5 θ |
Prestressing steel:
εp(θ) = −2,016 ×10−4 + 10−5 θ + 0,4 × 10−2 θ2 | for 20°C ≤ θ ≤ 1200°C |
where θ is the steel temperature (°C)
Figure 3.7: Thermal conductivity of concrete
Figure 3.8: Total thermal elongation of steel
Note 1: When calculation methods are used, reference is made to 4.6 for integrity function (E).
Note 2: For insulation function (I) the ambient temperature is normally assumed to be 20°C.
Note 3: The decision on the use of advanced calculation methods in a country may be found in its National Annex.
Note l: Informative Annex B provides two alternative methods, B.1 “500°C isotherm method” and B.2 “Zone method” for calculating the resistance to bending moments and axial forces. Second order effects may be included with both models. The two methods are applicable to structures subjected to a standard fire exposure. Method B.1 may be used in conjunction with both standard and parametric fires. Method B.2 is recommended for use with small sections and slender columns but is only valid for standard fires.
Note 2: Informative Annex C provides a zone method for analysing column sections with significant second order effects.
Note: Informative Annex D provides a simplified calculation method for shear, torsion and anchorage.
Note: Informative Annex E provides a simplified calculation method for the design of beams and slabs.
Note: The temperature profiles given in Annex A may be used to determine the temperatures in cross-sections with siliceous aggregate exposed to a standard fire up to the time of maximum gas temperature. The profiles are conservative for most other aggregates.
Note: Informative Annex B provides two methods using a reduced cross section.
The method described in Annex B.1 is based on the hypothesis that concrete at a temperature more than 500 °C is neglected in the calculation of load-bearing capacity, while concrete at a temperature below 500 °C is assumed to retain its full strength. This method is applicable to a reinforced and prestressed concrete section with respect to axial load, bending moment and their combinations.
The method described in Annex B.2 is based on the principle that cross-section is reduced by ignoring an ineffective zone at the fire-exposed surfaces.
The calculation should follow a specific procedure. The method is applicable to a reinforced and prestressed concrete section with respect to axial load, bending moment and their combinations.
Figure 4.1: Coefficient kc(θ) allowing for decrease of characteristic strength (fck) of concrete
31For compression reinforcement in columns and compressive zones of beams and slabs the strength reduction at 0,2% proof strain for Class N reinforcement should be used as given below. This strength reduction also applies for tension reinforcement where εs,fi < 2% when using simplified cross-section calculation methods (see Figure 4.2a, curve 3):
ks(θ) = 1,0 | for 20°C ≤ θ ≤ 100°C |
ks(θ) = 7,0 − 0,3 (θ − 400)/300 | for 100°C < θ ≤ 400°C |
ks(θ) = 0,57 − 0,13 (θ −700)/200 | for 500°C < θ ≤ 700°C |
ks(θ) = 0,1 (1200 − θ)/500 | for 700°C < θ ≤ 1200°C |
Similarly the strength reduction at 0,2% proof strain for Class X reinforcement may be used as given below. This strength reduction also applies for tension reinforcement where εs,fi < 2% (see Figure 4.2b, curve 2).
ks(θ) = 1,0 | for 20°C ≤ θ ≤ 100°C |
ks(θ) = 0,8 − 0,2 (θ −400)/300 | for 100°C < θ ≤ 400°C |
ks(θ) = 0,6 − 0,2 (θ −500)/100 | for 400°C < θ ≤ 500°C |
ks(θ) = 0,33 − 0,27 (θ −600)/100 | for 500°C < θ ≤ 600°C |
ks(θ) = 0,15 − 0,18 (θ −700)/100 | for 600°C < θ ≤ 700°C |
ks(θ) = 0,08 − 0,07 (θ −800)/100 | for 700°C < θ ≤ 800°C |
ks(θ) = 0,05 − 0,03 (θ −900)/100 | for 800°C < θ ≤ 900°C |
ks(θ) = 0,04 − 0,01 (θ −1000)/100 | for 900°C < θ ≤ 1000°C |
ks(θ) = 0,04 (1200 − θ)/200 | for 1000°C < θ ≤ 1200°C |
Figure 4.2a: Coefficient ks(θ) allowing for decrease of characteristic strength (fyk) of tension and compression reinforcement (Class N)
Figure 4.2b: Coefficient ks(θ) allowing for decrease of characteristic strength (fyk) of tension and compression reinforcement (Class X)
33Figure 4.3: Coefficient kp(θ) allowing for decrease of characteristic strength (βfpk) of prestressing steel
ε = εth + εσ + εcreep + εtr (4.1 5)
where
εth | is the thermal strain, |
εσ | is the instantaneous stress-dependent strain |
εcreep | breep is the creep strain and |
εtr | is the transient state strain |
Note: Informative Annex D provides a simplified calculations methods for shear, torsion and anchorage.
Note: The value of k for use in a Country may be found in its National Annex. The recommended value is 3.
Note: Where the number of bars is large enough, it may be assumed that an acceptable redistribution of stress is possible without loss of the stability (R). This includes:
Figure 4.4: Dimensions of gap at joints
For gaps with larger depth and, if necessary, with the addition of a sealing product, the fire resistance should be documented on the basis of an appropriate test procedure
Note: The tables have been developed on an empirical basis confirmed by experience and theoretical evaluation of tests. The data is derived from approximate conservative assumptions for the more common structural elements and is valid for the whole range of thermal conductivity in 3.3. More specific tabulated data can be found in the product standards for some particular types of concrete products or developed, on the basis of the calculation method in accordance with 4.2, 4.3 and 4.4.
If calcareous aggregates or lightweight aggregates are used in beams or slabs the minimum dimension of the cross-section may be reduced by 10%.
Ed,fi/Rd,fi ≤ 1,0 (5.1)
where:
Ed,fj | is the design effect of actions in the fire situation. |
Rd.fi | is the design load-bearing capacity (resistance) in the fire situation. |
Note: Where the partial safety factors specified in the National Annexes of EN 1990 deviate from those indicated in 2.4.2, the above value ηfi = 0,7 may not be valid. In such circumstances the value of ηfi for use in a Country may be found in its National Annex.
10 mm for prestressing bars, corresponding to θcr = 400°C
15 mm for prestressing wires and strands, corresponding to θcr = 350°C
Figure 5.1: Reference curves for critical temperature of reinforcing and prestressing steel θcr corresponding to the reduction factor ks(θcr) = σs,fi/fyk(20°C) or kp(θcr) = σp,fi/fpk(20°C)
These curves are derived as follows:
ks(θ) = 1,0 | for 20°C ≤ θ ≤ 350°C |
ks(θ) = 1,0 − 0,4 · (θ − 350)/150 | for 350°C < θ ≤ 500°C |
ks(θ) = 0,61 − 0,5 · (θ − 500)/200 | for 350°C < θ ≤ 500°C |
ks(θ) = 0,1 − 0,1 · (θ − 700)/500 | for 700°C < θ ≤ 1200°C |
kp(θ) = 1,0 | for 20°C ≤ θ ≤ 200°C |
kp(θ) = 1,0 − 0,45 · (θ − 200)/200 | for 200°C < θ ≤ 400°C |
kp(θ) = 0,55 − 0,45 · (θ − 400)/150 | for 400°C < θ ≤ 500°C |
kp(θ) = 0,1 − 0,1 · (θ − 550)/650 | for 550°C < θ ≤ 1200°C |
kp(θ) = 1,0 | for 20°C ≤ θ ≤ 200°C |
kp(θ) = 1,0 − 0,45 · (θ − 100)/250 | for 100°C < θ ≤ 350°C |
kp(θ) = 0,55 − 0,45 · (θ − 350)/200 | for 350°C < θ ≤ 550°C |
kp(θ) = 0,1 − 0,1 · (θ − 550)/650 | for 550°C < θ ≤ 1200°C |
where:
γs | is the partial safety factor for reinforcing steel (see Section 2 of EN 1992-1-1) |
As,req | is the area of reinforcement required for ultimate limit state according to EN 1992-1-1 |
As,prov | is the area of reinforcement provided |
Ed,fi/Ed | may be assessed using 2.4.2. |
Δa = 0,1 (500 - θcr) (mm) (5.3)
bmod ≥ bmin + 0,8 (400 - θcr) (mm) (5.4)
where bmin is the minimum dimension b given in the tables, related to the required standard fire resistance.
An alternative to increasing the width according to Expression (5.4) may be to adjust the axis distance of the reinforcement in order to obtain the temperature required for the actual stress. This requires using a more accurate method such as that given in Annex A.
Figure 5.2: Sections through structural members, showing nominal axis distance a
where:
Asi | is the cross sectional area of steel bar (tendon, wire) “i” |
ai | is the axis distance of steel bar (tendon, wire) “i” from the nearest exposed surface. |
When reinforcement consists of steels with different characteristic strength Asi should be replaced by Asi fyki (or Asi fpki) in Expression (5.5).
41Note: Use of temperature graphs and simplified calculation methods is recommended.
Figure 5.3: Dimensions used to calculate average axis distance am
Note: Tabulated data is given for braced structures only. Tabulated data for unbraced structures may be found in a Country’s National Annex.
Note 1:
The value of emax, within limits 0,15h (or b) ≤ emax ≤ 0,4h (or b), for use in a Country may be found in its National Annex. The recommended value is 0,15h (or b).
Note 2: The effective length of a column under fire conditions lo,fi may be assumed to be equal to l0 at normal temperature in all cases. For braced building structures where the required Standard fire exposure is higher than 30 minutes, the effective length l0,fi may be taken as 0,5 l for intermediate floors and 0,5 l ≤ l0,fi ≤ 0,7l for the upper floor, where l is the actual length of the column (centre to centre).
42Note 3: First order eccentricity under fire conditions may be assumed as equal to that in normal temperature design.
μfi = NEd.fi/NRd (5.6)
where
NEd.fi | is the design axial load in the fire situation, |
NRd | is the design resistance of the column at normal temperature conditions |
NRd is calculated according to EN 1992-1-1 with γm for normal temperature design, including second order effects and an initial eccentricity equal to the eccentricity of NEd.fi.
Note 1: The reduction factor ηfi may be used instead of μfi, for the design load level (see 2.4.2) as a safe simplification since ηfi assumes that the column is fully loaded at normal temperature design.
Standard fire resistance | Minimum dimensions (mm) Column width bmin/axis distance a of the main bars |
|||
Column exposed on more than one side | Exposed on one side | |||
μfi = 0.2 | μfi = 0.5 | μfi = 0.7 | μfi = 0.7 | |
1 | 2 | 3 | 4 | 5 |
R30 | 200/25 | 200/25 | 200/32 300/27 |
155/25 |
R60 | 200/25 | 200/36 300/31 |
250/46 350/40 |
155/25 |
R90 | 200/31 300/25 |
300/45 400/38 |
350/53 450/40** |
155/25 |
R 120 | 250/40 350/35 |
350/45** 450/40** |
350/57** 450/51** |
175/35 |
R 180 | 350/45** | 350/63** | 450/70** | 230/55 |
R240 | 350/61** | 450/75** | − | 295/70 |
** Minimum 8 bars |
Note: Table 5.2a is based on recommended value αcc =1,0.
R = 120 ((Rηfi + Ra + Rl + Rb + Rn)/120)1,8 (5.7)
where
Ra | = 1,60 (a - 30) |
Rl | = 9,60 (5 - /0,fi) |
Rb | = 0.09 b’ |
Rn | = 0 for n = 4 (corner bars only) |
= 12 for n > 4 | |
a | is the axis distance to the longitudinal steel bars (mm); 25 mm ≤ a ≤ 80 mm |
l0,fi | is the effective length of the column under fire conditions; 2 m ≤ l0,fi ≤ 6 m; values corresponding to l0,fi = 2 m give safe results for columns with l0,fi < 2 m |
b’ | = 2Ac/ (b+h) for rectangular cross-sections or the diameter of circular cross sections |
200 mm ≤ b’ ≤ 450 mm; h ≤ 1,5 b. | |
ω | denotes the mechanical reinforcement ratio at normal temperature conditions: |
αcc | is coefficient for compressive strength (see EN 1992-1-1) |
For first order eccentricity under fire conditions the limits of validity given in 5.3.2 (2) apply.
the load level, n, at normal temperature conditions (see EN 1992-1-1, 5.8) is given by
n = N0Ed.fi /(0,7(Ac fcd + As fyd)) (5.8a)
the first order eccentricity under fire conditions, e, is given by
e = M0Ed,fi/(N0Ed,fi) (5.8b)
e / b has been taken as ≤ 0,25 with emax = 100 mm
the slenderness of the column under fire conditions, λfi, is given by
λfi = l0,fi/i (5.8c)
λfi has been taken as ≤ 30, which covers the majority of columns in normal buildings
where
l0,fi | is the effective length of the column under fire conditions |
b | is the minimum dimension of the section on rectangular columns or the diameter on circular columns 44 |
N0,Ed,fi, M0,Ed,fi | is the axial load and first order moment under fire conditions |
ω | is the mechanical reinforcement ratio at normal temperature conditions: |
i | is the minimum radius of inertia |
Note 1: N0Ed.fi may be taken as 0,7 N0Ed (ηfi = 0,7, see 2.4.2) unless ηfi is calculated explicitly).
Note 2: Slenderness ratio λfi under fire conditions may be assumed as equal to λ at normal temperature in all cases. For braced building structures where the required Standard fire exposure is higher than 30 minutes, the effective length l0,fi may be taken as 0,5 / for intermediate floors and 0,5 l ≤ l0,fi ≤ 0,7 / for the upper floor, where / is the actual length of the column (centre to centre).
Standard fire resistance | Mechanical reinforcement ratio ω | Minimum dimensions (mm). Column width bmin/axis distance a | |||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 0,100 0,500 1,000 |
150/25* 150/25* 150/25* |
150/25* 150/25* 150/25* |
200/30:250/25* 150/25* 150/25* |
300/30:350/25* 200/30:250/25* 200/30:300/25* |
R 60 | 0,100 0,500 1,000 |
150/30:200/25* 150/25* 150/25* |
200/40:300/25* 150/35:200/25* 150/30:200/25* |
300/40:500/25* 250/35:350/25* 200/40:400/25* |
500/25* 350/40:550/25* 300/50:600/30 |
R90 | 0,100 0,500 1,000 |
200/40:250/25* 150/35:200/25* 200/25* |
300/40:400/25* 200/45:300/25* 200/40:300/25* |
500/50:550/25* 300/45:550/25* 250/40:550/25* |
550/40:600/25* 500/50:600/40 500/50:600/45 |
R120 | 0,100 0,500 1,000 |
250/50:350/25* 200/45:300/25* 200/40:250/25* |
400/50:550/25* 300/45:550/25* 250/50:400/25* |
550/25* 450/50:600/25* 450/45:600/30 |
550/60:600/45 500/60:600/50 600/60 |
R 180 | 0,100 0,500 1,000 |
400/50:500/25* 300/45:450/25* 300/35:400/25* |
500/60:550/25* 450/50:600/25* 450/50:550/25* |
550/60:600/30 500/60:600/50 500/60:600/45 |
(1) 600/75 (1) |
R240 | 0,100 0,500 1,000 |
500/60:550/25* 450/45:500/25* 400/45:500/25* |
550/40:600/25* 550/55:600/25* 500/40:600/30 |
600/75 600/70 600/60 |
(1) (1) (1) |
* Normally the cover required by EN 1992-1-1 will control.
|
Standard fire resistance | Minimum wall thickness (mm) |
1 | 2 |
El 30 | 60 |
El 60 | 80 |
El 90 | 100 |
El 120 | 120 |
El 180 | 150 |
El 240 | 175 |
Note: Ratio of clear height of wall to wall thickness is limited to 40 in 54.1 (3). Clear height of wall indudes limitation that Tabulated data for walls is valid for braced structures only, see corresponding limitation for columns in 5.3.1.
Standard fire resistance | Minimum dimensions (mm) Wall thickness/axis distance for | |||
μfi = 0,35 | μfi = 0,7 | |||
wall exposed on one side | wall exposed on two sides | wall exposed on one side | wall exposed on two sides | |
1 | 2 | 3 | 4 | 5 |
REI 30 | 100/10* | 120/10* | 120/10* | 120/10* |
REI 60 | 110/10* | 120/10* | 130/10* | 140/10* |
REI 90 | 120/20* | 140/10* | 140/25 | 170/25 |
REI 120 | 150/25 | 160/25 | 160/35 | 220/35 |
REI 180 | 180/40 | 200/45 | 210/50 | 270/55 |
REI 240 | 230/55 | 250/55 | 270/60 | 350/60 |
* Normally the cover required by EN 1992-1-1 will control. | ||||
Note: For the definition of μfi see 5.3.2 (3). |
200 mm for unreinforced wall
140 mm for reinforced load-bearing wall
120 mm for reinforced non load bearing wall
and the axis distance of the load-bearing wall should not be less than 25 mm.
Note: The choice of Class WA, WB or WC for use in a Country may be found in its National Annex.
deff = d1 + 0,5 d2 ≥ bmin (5.9)
where bmin is the minimum value of beam width according to Table 5.5.
Figure 5.4: Definition of dimensions for different types of beam section
This rule does not apply if an imaginary cross section ((c) in Figure 5.5) which fulfils the minimum requirements with regard to fire resistance and which includes the whole reinforcement can be drawn inside the actual cross section.
where:
deff is given by Expression (5.9)
bmin is the minimum beam width given in Table 5.5.
Figure 5.5: l-shaped beam with increasing web width bw satisfying the requirements of an imaginary cross-section.
Note: Table 5.6 may be used for continuous beams where moment redistribution is more than 15%, provided that there is sufficient rotational capacity at the supports for the required fire exposure conditions. More rigorous calculations may be based on simplified calculation methods (e.g. Annex E), when applicable, to determine more accurate values of the axis distance and curtailment length of top and bottom reinforcement.
As,req(X) = As,req(0) · (1 − 2,5x/leff) (5.11)
where:
x | is the distance from the section considered to the centre line of the support where x ≤ 0,3leff |
As,req(0) | is the area of top reinforcement required over the support, according to EN 1992-1-1 |
As,req(X) | is the minimum area of top reinforcement required in the section at distance (x) from the centreline of the support considered but not less than As(x) required by EN 1992-1-1. |
/eff | is the effective length of span. If the effective length of the adjacent spans is larger then this value should be used. |
Figure 5.6: Envelope of resisting bending moments over supports for fire conditions.
50Standard fire resistance | Minimum dimensions (mm) | ||||||
Possible combinations of a and bmin where a is the average axis distance and bmin is the width of beam | Web thickness bw | ||||||
Class WA | Class WB | Class WC | |||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
R 30 | bmin= 80 a = 25 |
120 20 |
160 15* |
200 15* |
80 | 80 | 80 |
R 60 | bmin= 120 a = 40 |
160 35 |
200 30 |
300 25 |
100 | 80 | 100 |
R 90 | bmin= 150 a = 55 |
200 45 |
300 40 |
400 35 |
110 | 100 | 100 |
R 120 | bmin= 200 a = 65 |
240 60 |
300 55 |
500 50 |
130 | 120 | 120 |
R 180 | bmin= 240 a = 80 |
300 70 |
400 65 |
600 60 |
150 | 150 | 140 |
R240 | bmin= 280 a = 90 |
350 80 |
500 75 |
700 70 |
170 | 170 | 160 |
asd = a + 10mm (see note below) | |||||||
For prestressed beams the increase of axis distance according to 5.2(5) should be noted. | |||||||
asd is the axis distance to the side of beam for the corner bars (or tendon or wire) of beams with only one layer of reinforcement. For values of bmm greater than that given in Column 4 no increase of asd is required. | |||||||
* Normally the cover required by EN 1992-1-1 will control. |
Standard fire resistance | Minimum dimensions (mm) | ||||||
Possible combinations of a and bmin where a is the average axis distance and bmin is the width of beam | Web thickness bw | ||||||
Class WA | Class WB | Class WC | |||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
R 30 | bmin= 80 a = 15* |
160 12* |
80 | 80 | 80 | ||
R 60 | bmin= 120 a = 25 |
200 12* |
100 | 80 | 100 | ||
R 90 | bmin= 150 a = 35 |
250 25 |
110 | 100 | 100 | ||
R 120 | bmin= 200 a = 45 |
300 35 |
450 35 |
500 30 |
130 | 120 | 120 |
R 180 | bmin= 240 a = 60 |
400 50 |
550 50 |
600 40 |
150 | 150 | 140 |
R240 | bmin= 280 a = 75 |
500 60 |
650 60 |
700 50 |
170 | 170 | 160 |
asd = a + 10mm (see note below) | |||||||
For prestressed beams the increase of axis distance according to 5.2(5) should be noted. | |||||||
asd is the axis distance to the side of beam for the corner bars (or tendon or wire) of beams with only one layer of reinforcement. For values of bmin greater than that given in Column 3 no increase of asd is required. |
|||||||
* Normally the cover required by EN 1992-1-1 will control. |
Standard fire resistance | Minimum beam width bmin (mm) and web thickness bw (mm) |
1 | 2 |
R 120 | 220 |
R 180 | 380 |
R240 | 480 |
Ac = 2b2min (5.12)
where bmin is given by Tables 5.5 to 5.7.
Figure 5.7: Concrete slab with floor finishes
Standard fire resistance | Minimum dimensions (mm) | |||
slab thickness hs (mm) | axis-distance a | |||
one way | two way: | |||
/y//x≤1,5 | 1,5</y//x≤2 | |||
1 | 2 | 3 | 4 | 5 |
REI 30 | 60 | 10* | 10* | 10* |
REI 60 | 80 | 20 | 10* | 15* |
REI 90 | 100 | 30 | 15* | 20 |
REI 120 | 120 | 40 | 20 | 25 |
REI 180 | 150 | 55 | 30 | 40 |
REI 240 | 175 | 65 | 40 | 50 |
/x and /y are the spans of a two-way slab (two directions at right angles) where /y is the longer span. | ||||
For prestressed slabs the increase of axis distance according to 5.2(5) should be noted. | ||||
The axis distance a in Column 4 and 5 for two way slabs relate to slabs supported at all four edges. Otherwise, they should be treated as one-way spanning slab. | ||||
* Normally the cover required by EN 1992-1-1 will control. |
The rules in 5.6.3 (3) for continuous beams also apply to continuous slabs. If these rules are not followed each span of a continuous slab should be assessed as a simply supported slab as above.
Note: Additional rules on rotation capacity on supports may be given in National Annex.
Figure 5.8: Slab systems for which minimum reinforcement areas according to 5.7.3 (3) should be provided.
55Standard fire resistance | Minimum dimensions (mm) | |
---|---|---|
slab-thickness hs | axis-distance a | |
1 | 2 | 3 |
REI 30 | 150 | 10* |
REI 60 | 180 | 15* |
REI 90 | 200 | 25 |
REI 120 | 200 | 35 |
REI 180 | 200 | 45 |
REI 240 | 200 | 50 |
* Normally the cover required by EN 1992-1-1 will control. |
Standard fire resistance | Minimum dimensions (mm) | |||
Possible combinations of width of ribs bmin and axis distance a | Slab thickness hs and axis distance a in flange | |||
1 | 2 | 3 | 4 | 5 |
REI 30 | bmin = 80 a = 15* |
hs = 80 a = 10* |
||
REI 60 | bmin = 100 a = 35 |
120 25 |
≥200 15* |
hs=80 a = 10* |
REI 90 | bmin = 120 a = 45 |
160 40 |
≥250 30 |
hS = 100 a = 15* |
REI 120 | bmin= 160 a = 60 |
190 55 |
≥300 40 |
hs= 120 a = 20 |
REI 180 | bmin = 220 a = 75 |
260 70 |
≥410 60 |
hs= 150 a = 30 |
REI 240 | bmin = 280 a = 90 |
350 75 |
≥500 70 |
hs = 175 a = 40 |
asd = a + 10 | ||||
asd denotes the distance measured between the axis of the reinforcement and lateral surface of the rib exposed to fire. | ||||
* Normally the cover required by EN 1992-1-1 will control. |
Standard fire resistance | Minimum dimensions (mm) | |||
---|---|---|---|---|
Possible combinations of width of ribs bmin and axis distance a | Slab thickness hs and axis distance a in flange | |||
1 | 2 | 3 | 4 | 5 |
REI 30 | bmin = 80 a = 10* |
hs= 80 a = 10* |
||
REI 60 | bmin = 100 a = 25 |
120 15* |
≥200 10* |
h5=80 a = 10* |
REI 90 | bmin = 120 a = 35 |
160 25 |
≥250 15* |
hs= 100 a = 15* |
REI 120 | bmin = 160 a = 45 |
190 40 |
≥300 30 |
hs= 120 a = 20 |
REI 180 | bmin = 310 a = 60 |
600 50 |
hs = 150 a = 30 |
|
REI 240 | bmin = 450 a = 70 |
700 60 |
hs = 175 a = 40 |
|
asd = a + 10 | ||||
asd denotes the distance measured between the axis of the reinforcement and lateral surface of the rib exposed to fire. | ||||
* Normally the cover required by EN 1992-1-1 will control |
Note: Where the actual characteristic strength of concrete is likely to be of a higher class than that specified in design, the relative reduction in strength for the higher class should be used for fire design.
Note: The values fc,θ/ fck for use in a Country may be found in its National Annex. Three classes are given in Table 6.1 N. However the values given for each rely on a limited amount of test results. The selection and limit of use of these classes to certain strength classes or type of concrete for use in a Country may be found in its National Annex. The recommended class for concrete C 55/67 and C 60/75 is Class 1, for concrete C 70/85 and C80/95 is Class 2 and for concrete C90/105 is Class 3. See also note to 6.4.2.1 (3) and 6.4.2.2 (2).
Concrete temperature θ °C | fc,θ/ fck | ||
Class 1 | Class 2 | Class 3 | |
20 | 1,00 | 1,0 | 1,0 |
50 | 1,00 | 1,0 | 1,0 |
100 | 0,90 | 0,75 | 0,75 |
200 | 0,70 | ||
250 | 0,90 | ||
300 | 0,85 | 0,65 | |
400 | 0,75 | 0,75 | 0,45 |
500 | 0,30 | ||
600 | 0,25 | ||
700 | |||
800 | 0,15 | 0,15 | 0,15 |
900 | 0,08 | 0,08 | |
1000 | 0,04 | 0,04 | |
1100 | 0,01 | 0,01 | |
1200 | 0,00 | 0,00 | 0,00 |
Method A: A reinforcement mesh with a nominal cover of 15 mm. This mesh should have wires with a diameter ≥ 2 mm with a pitch ≤ 50 × 50 mm. The nominal cover to the main reinforcement should be ≥ 40 mm.
59Method B: A type of concrete for which it has been demonstrated (by local experience or by testing) that no spalling of concrete occurs under fire exposure.
Method C: Protective layers for which it is demonstrated that no spalling of concrete occurs under fire exposure.
Method D: Include in the concrete mix more than 2 kg/m3 of monofilament propylene fibres.
Note: The selection of Methods to be used in a Country may be found in its National Annex.
Note 1: The value of thermal conductivity for high strength concrete for use in a Country may be given in its National Annex within the range defined by lower and upper limit in clause 3.3.3.
Note 2: Thermal conductivity of high strength concrete may be higher than that for normal strength concrete.
az = k az, 500 (6.4)
60Note: k allows for the conversion from the 500°C to the 460°C isotherm depth for Class 1 in Table 6.1 N, and to the 400°C isotherm depth for Class 2 in Table 6.1 N. The value of k for use in a Country may be found in its National Annex. The recommended value is 1,1 for Class 1 and 1,3 for Class 2. For Class 3 more accurate methods are recommended.
Md,fi = M500 · km (6.5)
where
Md,fi | is the design moment capacity in the fire situation |
M500 | is the calculated moment capacity based on the |
km | is a reduction factor |
Note: The value of km, which depends on the reduction strength given in Table 6.1 N, for use in a Country may be found in its National Annex. The recommended value is given in Table 6.2N. For Class 3 more accurate methods are recommended
Item | km | |
---|---|---|
Class 1 | Class 2 | |
Beams | 0,98 | 0,95 |
Slabs exposed to fire in the compression zone | 0,98 | 0,95 |
Slabs exposed to fire in the tension side, h1 ≥ 120 mm | 0,98 | 0,95 |
Slabs exposed to fire in the tension side, h1 = 50 mm where h1 is the concrete slab thickness (see Figure 5.7) |
0,95 | 0,85 |
Where
62k is the factor given in 6.4.2.1(3)
a is axis distance required in Section 5.
Note: For columns the degree of utilisation in the fire situation μfi or load level of a column at normal temperature conditions n should be defined before calculating the increase of the cross-section dimensions by 2(k − 1)a
(informative)
Note: the lower limit of thermal conductivity has been derived from comparisons with temperatures measured in fire tests of different types of concrete structures, the lower limit gives more realistic temperatures for concrete structures than the upper limit, which has been derived from tests for steel/concrete composite structures.
Figure A.1: Area of cross-section for which the temperature profiles are presented
63Figure A.2: Temperature profiles for slabs (height h = 200) for R60 - R240
64Figure A.3: Temperature profiles (°C) for a beam, h × b = 150 × 80 − R30
Figure A.4: Temperature profiles (°C) for a beam, h × b = 300 × 160
65Figure A.5: Temperature profiles (°C) for a Figure A.6: 500 C isotherms for a beam, beam, h × b = 300 × 160 h × b = 300 × 160
66Figure A.7: Temperature profiles (°C) for a beam h × b = 600 × 300
Figure A.8 Temperature profiles (°C) for a beam h × b = 600 × 300 − R120
67Figure A.9: Temperature profiles (°C) for a beam h × b = 800 × 500
Figure A.10: Temperature profiles (°C) for a beam h × b = 800 × 500"
68Figure A.11: Temperature profiles (°C) for a column, h × b = 300 × 300 − R30
Figure A.12: Temperature profiles (°C) for a column, h × b = 300 × 300 − R60
Figure A.13: Temperature profiles (°C) for a column, h × b = 300 × 300 − R90
Figure A.14: Temperature profiles (°C) for a column, h × b = 300 × 300 − R120
69Figure A.15: 500 °C isotherms for a column, h × b = 300 × 300
Figure A.16: Temperature profiles (°C) for a circular column, 300 dia − R30
Figure A.17: Temperature profiles (°C) for a circular column, 300 dia − R60
70Figure A.18: Temperature profiles (°C) for a circular column, 300 dia − R90
Figure A.19: Temperature profiles (°C) for a circular column, 300 dia − R120
Figure A.20: 500 °C isotherms for a circular column, 300 dia
71(Informative)
|
Figure B.1. Reduced cross-section of reinforced concrete beam and column
Figure B.2. Stress distribution at ultimate limit state for a rectangular concrete cross-section with compression reinforcement.
74The average reduced strength of a reinforcement layer with respect to increased temperatures, is calculated in accordance with Expression (B.1).
where,
θ | is the temperature in reinforcement bar i |
k(θi) | is a reduction of the strength of the reinforcement bar i due to the temperature θi which is obtained from Figure 4.11 |
kv(θ) | is the average reduction of the strength of reinforcement layer v |
nv | is the number of reinforcement bars in layer v |
Where
is the axis distance from the bottom surface of the reduced cross-section to reinforcement layer v |
The average steel strength of a reinforcement group, k(φ) fsd,fi, with respect to increased temperatures, may be calculated using Expression (B.4)
Where
ks(θi) | is a reduction of the strength of reinforcement bar i |
fsd,i | is the design strength of reinforcement bar i |
Ai | is the cross-section area of reinforcement bar i |
The axis distance, a to the centroid of the reinforcement group is calculated in accordance with Expression (B.5).
Where
is the axis distance from reduced cross-section to reinforcement bar i |
Mu1 = As1fsd,fi(θm)z (B.6)
Mu2 = As2 fscd,fi(θm)·z′ (B.8)
As = As1 + As2 (B.9)
Where
As | is the total reinforcement area |
fsd,fi | is the design tensile strength of reinforcement |
fscd,fi | is the design strength for compressive reinforcement |
ωk | is the design strength ratio of reinforcement for the fire-exposed cross-section |
bfi | is the width of the fire exposed cross-section |
dfi | is the efficient height of the fire exposed cross-section |
fcd,fi(20) | is the design compressive strength of concrete (at normal temperature) |
z | is the lever arm between tension reinforcement and concrete |
z′ | is the lever between tension and compression reinforcement |
θm | is the mean temperature of the reinforcement layer |
When the moment contributions are assessed as shown above the total moment capacity is obtained from
Mu = Mu1 + Mu2 (B.10)
a width equal to 2w (see Figure B.3 (d)). The flange of Figure B.3 (f) is related to the equivalent slab in Figure B.3 (c), and the web to the equivalent wall in Figure B.3 (a).
The reduction of the cross-section is based on a damaged zone of thickness az at the fire exposed surfaces which is calculated as follows:
Figure B.3. Reduction of strength and cross-section for sections exposed to fire
77Figure B.4. Division of a wall, with both sides exposed to fire, into zones for use in calculation of strength reduction and az values
where
n | is the number of parallel zones in width w |
w | is half the total width |
m | is the zone number |
Where kc(θM) denotes the reduction coefficient for concrete at point M.
Figure B.5: Reduction in cross section and concrete strength assuming standard temperature-time curve
79(EI)z = [Kc(θM)]2 · Ec · Iz
where
kc(θM) | is a reduction coefficient for concrete at point M (see B.2) |
Ec | is the elastic modulus of the concrete at normal temperature |
Iz | is the 2nd moment of area of the reduced section |
The elastic modulus of the reinforcement is Es,θ (see Table 3.2)
Figure B6: Dividing cross-section of column into zones with approximate uniform temperature
Figure B7: Determination of ultimate moment capacity (MRd,fi), second order moment (M2,fi) and ultimate first order moment capacity (M0Rd,fi)
81(informative)
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 150/25* | 150/25* |
40 | 150/25* | 150/25* | 150/25* | 150/25* | |
50 | 150/25* | 150/25* | 150/25* | 200/25* | |
60 | 150/25* | 150/25* | 200/25* | 250/25* | |
70 | 150/25* | 150/25* | 250/25* | 300/25* | |
80 | 150/25* | 200/25* | 250/30:300/25* | 350/25* | |
R 60 | 30 | 150/25* | 150/25* | 200/25* | 200/30:250/25* |
40 | 150/25* | 150/25* | 200/25* | 250/25* | |
50 | 150/25* | 200/25* | 250/25* | 300/25 | |
60 | 150/25* | 200/40:250/25* | 250/40:300/25* | 350/30:400/25* | |
70 | 200/25* | 250/30:300/25* | 300/40:350/25* | 450/35:550/25* | |
80 | 200/30:250/25* | 250/40:300/25* | 400/30:450/25* | 550/60:600/35 | |
R 90 | 30 | 150/25* | 200/25* | 200/50:250/25* | 250/30:300/25* |
40 | 150/35:200/25* | 200/30:250/25* | 250/25* | 300/25 | |
50 | 200/25* | 250/25* | 300/25* | 350/50:400/25* | |
60 | 200/35:250/25* | 250/40:300/25* | 350/35:400/25* | 450/50:550/25* | |
70 | 250/25* | 300/35:350/25* | 400/45:550/25* | 600/40 | |
80 | 250/30:300/25* | 350/35:400/25* | 550/40:600/25* | (1) | |
R 120 | 30 | 200/25* | 250/25* | 250/25* | 300/45:350/25 |
40 | 250/25* | 250/25* | 300/25* | 400/25* | |
50 | 250/25* | 300/25* | 350/50:400/25* | 450/50:500/25* | |
60 | 250/25* | 350/25* | 450/400:500/25* | 550/50 | |
70 | 250/50:300/25* | 400/25* | 500/60:550/25* | (1) | |
80 | 300/25* | 450/40:500/25* | 600/45 | (1) | |
R 180 | 30 | 250/25* | 250/25* | 350/25* | 400/50:450/25* |
40 | 250/25* | 300/30:350/25* | 400/25* | 450/50:500/25* | |
50 | 250/50:300/25* | 350/50:400/25* | 450/40:500/25* | 550/60:600/35 | |
60 | 300/40:350/25* | 450/25* | 550/40:600/25 | (1) | |
70 | 350/30:400/25* | 500/25* | 600/80 | (1) | |
80 | 400/30:450/25* | 550/45/600/25* | (1) | (1) | |
R240 | 30 | 250/25* | 350/25* | 450/25* | 500/40:550/25* |
40 | 300/25* | 400/25* | 500/25* | 600/25* | |
50 | 350/25* | 450/25* | 550/50:600/25* | (1) | |
60 | 400/25* | 500/60:550/25* | 600/80 | (1) | |
70 | 450/25* | 600/25* | (1) | (1) | |
80 | 500/25* | 600/80 | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
|
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 200/30:250/25* | 300/30:350/25* |
40 | 150/25* | 150/30:200/25* | 300/25* | 500/40:550/25* | |
50 | 150/25 | 200/40:250/25* | 350/40:500/25* | 550/25* | |
60 | 150/25* | 300/25* | 550/25* | 600/30 | |
70 | 200/25* | 350/40:500/25* | 550/30:600/25* | (1) | |
80 | 250/25* | 550/25* | (1) | (1) | |
R 60 | 30 | 150/30:200/25* | 200/40:300/25* | 300/40:500/25* | 500/25* |
40 | 200/30:250/25* | 300/35:350/25* | 450/50:550/25* | 550/40:600/25* | |
50 | 200/40:300/25* | 350/45:550/25* | 550/30:600/30 | 600/55 | |
60 | 250/35:400/25* | 450/50:550/25* | 600/35 | (1) | |
70 | 300/40:500/25* | 550/30:600/25* | 600/80 | (1) | |
80 | 400/40:550/25* | 600/30 | (1) | (1) | |
R 90 | 30 | 200/40:250/25* | 300/40:400/25* | 500/50:550/25* | 550/40:600/25* |
40 | 250/40:350/25* | 350/50:550/25* | 550/35:600/25* | 600/50 | |
50 | 300/40:500/25* | 500/60:550/25* | 600/40 | (1) | |
60 | 300/50:550/25* | 550/45:600/25* | (1) | (1) | |
70 | 400/50:550/25* | 600/45 | (1) | (1) | |
80 | 500/60/600/25* | (1) | (1) | (1) | |
R120 | 30 | 250/50:350/25* | 400/50:550/25* | 550/25* | 550/60:600/45 |
40 | 300/50:500/25* | 500/50:550/25* | 550/50:600/25 | (1) | |
50 | 400/50:550/25* | 550/50:600/25* | 600/60 | (1) | |
60 | 500/50:550/25* | 550/55:600/50 | (1) | (1) | |
70 | 500/60:600/25* | 600/60 | (1) | (1) | |
80 | 550/50:600/25* | (1) | (1) | (1) | |
R 180 | 30 | 400/50:500/25* | 500/60:550/25* | 550/60:600/30 | (1) |
40 | 500/50:550/25* | 550/50:600/25* | 600/80 | (1) | |
50 | 550/25* | 600/60 | (1) | (1) | |
60 | 550/50:600/25* | 600/80 | (1) | (1) | |
70 | 600/55 | (1) | (1) | (1) | |
80 | 600/70 | (1) | (1) | (1) | |
R 240 | 30 | 500/60:550/25* | 550/40:600/25* | 600/75 | (1) |
40 | 550/25* | 600/60 | (1) | (1) | |
50 | 550/60:600/25* | 600/80 | (1) | (1) | |
60 | 600/60 | (1) | (1) | (1) | |
70 | 600/80 | (1) | (1) | (1) | |
80 | (1) | (1) | (1) | (1) | |
* Normally the cover required by prEN 1992-1-1 will control. | |||||
|
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 400/40:550/25* | 550/25* | (1) |
40 | 200/25* | 550/25* | 550/35:600/30 | (1) | |
50 | 250/30:300/25* | 550/30:600/25* | (1) | (1) | |
60 | 300/40:550/25* | 600/50 | (1) | (1) | |
70 | 400/40:550/25* | (1) | (1) | (1) | |
80 | 550/25 | (1) | (1) | (1) | |
R 60 | 30 | 300/35:500/25* | 500/50:550/25* | 550/50:600/40 | (1) |
40 | 350/40:550/25* | 550/40:600/30 | (1) | (1) | |
50 | 450/50:550/25* | 550/50:600/40 | (1) | (1) | |
60 | 550/30 | 600/80 | (1) | (1) | |
70 | 550/35 | (1) | (1) | (1) | |
80 | 550/40 | (1) | (1) | (1) | |
R 90 | 30 | 350/50:550/25* | 550/45:600/40 | 600/80 | (1) |
40 | 500/60:600/30 | 550/60:600/50 | (1) | (1) | |
50 | 550/40 | 600/80 | (1) | (1) | |
60 | 550/50:600/45 | (1) | (1) | (1) | |
70 | 550/60:600/50 | (1) | (1) | (1) | |
80 | 600/70 | (1) | (1) | (1) | |
R 120 | 30 | 550/40:600/30 | 550/50 | (1) | (1) |
40 | 550/50:600/45 | 600/70 | (1) | (1) | |
50 | 550/55:600/50 | (1) | (1) | (1) | |
60 | 550/60:600/50 | (1) | (1) | (1) | |
70 | 600/70 | (1) | (1) | (1) | |
80 | (1) | (1) | (1) | (1) | |
R 180 | 30 | 550/50 | 600/80 | (1) | (1) |
40 | 550/60 | (1) | (1) | (1) | |
50 | 600/70 | (1) | (1) | (1) | |
60 | (1) | (1) | (1) | (1) | |
70 | (1) | (1) | (1) | (1) | |
80 | (1) | (1) | (1) | (1) | |
R 240 | 30 | 600/70 | (1) | (1) | (1) |
40 | (1) | (1) | (1) | (1) | |
50 | (1) | (1) | (1) | (1) | |
60 | (1) | (1) | (1) | (1) | |
70 | (1) | (1) | (1) | (1) | |
80 | (1) | (1) | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
Requires a width greater than 600 mm. Particular assessment for buckling is required. |
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 150/25* | 150/25* |
40 | 150/25* | 150/25* | 150/25* | 150/25* | |
50 | 150/25* | 150/25* | 150/25* | 200/25* | |
60 | 150/25* | 150/25* | 150/25* | 200/30:250/25* | |
70 | 150/25* | 150/25* | 200/25* | 250/25* | |
80 | 150/25* | 150/25* | 200/30:250/25* | 300/25* | |
R 60 | 30 | 150/25* | 150/25* | 150/30:200/25* | 200/35:250/25* |
40 | 150/25* | 150/25* | 200/25* | 250/30:300/25* | |
50 | 150/25* | 150/35:200/25* | 200/40:250/25* | 250/40:350/25* | |
60 | 150/25* | 200/30:250/25* | 250/30:300/25* | 300/40:450/25 | |
70 | 150/25* | 200/35:250/25* | 250/40:350/25* | 350/45:600/25 | |
80 | 150/35:200/25* | 250/30:300/25* | 300/40:500/25* | 450/50:600/35 | |
R 90 | 30 | 150/25* | 150/40:200/25* | 200/40:250/25* | 250/40:300/25* |
40 | 150/25* | 200/35:250/25* | 250/30:300/25* | 300/40:400/25* | |
50 | 150/40:200/25* | 200/45:250/25* | 250/45:350/25* | 350/45:550/25* | |
60 | 200/25* | 250/35:300/25* | 300/45:400/25* | 400/50:600/35 | |
70 | 200/35:250/25* | 250/45:350/25* | 350/45:600/25* | 550/50:600/45 | |
80 | 200/45:250/25* | 250/50:400/25* | 400/50:600/35 | 600/60 | |
R 120 | 30 | 150/35:200/25* | 200/40:250/25* | 250/45:300/25* | 350/45:500/25* |
40 | 200/25* | 250/25* | 300/45:350/25* | 400/50:550/25* | |
50 | 200/40:250/25* | 250/45:300/25* | 350/45:450/25* | 450/50:600/25* | |
60 | 200/50:250/25* | 300/45:350/25* | 400/50:550/25* | 500/60:600/35 | |
70 | 250/35:300/25* | 350/45:450/25* | 500/50:600/40 | 600/45 | |
80 | 250/45:300/25* | 400/50:550/25 | 500/60:600/45 | 600/60 | |
R 180 | 30 | 200/45:250/25* | 250/35:300/25* | 350/45:400/25* | 450/45:500/25* |
40 | 250/25* | 300/45:350/25* | 450/25* | 500/55:600/50 | |
50 | 250/35:300/25* | 350/45:400/25* | 500/40:550/25 | 600/65 | |
60 | 300/40:350/25* | 450/25* | 500/60:600/55 | 600/80 | |
70 | 350/25* | 500/40:550/25* | 600/65 | (1) | |
80 | 400/30:450/25* | 500/55:600/45 | 600/80 | (1) | |
R 240 | 30 | 250/25* | 350/25* | 450/45:500/25* | 550/65:600/50 |
40 | 250/40:300/25* | 400/45:450/25* | 500/60:550/25* | 600/75 | |
50 | 350/30:400/25* | 450/50:500/25* | 550/70:600/55 | (1) | |
60 | 400/35:450/25* | 500/50:600/25* | 600/75 | (1) | |
70 | 450/30:500/25* | 550/75:600/50 | (1) | (1) | |
80 | 500/40:550/25* | 600/70 | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
|
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 150/25* | 200/30:250/25* |
40 | 150/25* | 150/25* | 150/25* | 300/45:350/25* | |
50 | 150/25* | 150/25* | 200/30:250/25* | 350/40:450/25* | |
60 | 150/25* | 150/25* | 250/30:300/25* | 500/30:550/25* | |
70 | 150/25* | 150/35:200/25* | 350/30:400/25 | 550/35:600/30 | |
80 | 150/25* | 200/30:250:25* | 400/40:500/25 | 600/50 | |
R 60 | 30 | 150/25* | 150/35:200/25* | 250/35:350/25* | 350/40:550/25 |
40 | 150/25* | 200/30:300/25* | 300/35:500/25* | 450/50:600/30 | |
50 | 150/30:200/25* | 200/40:350/25* | 300/45:550/25* | 500/50:600/35 | |
60 | 150/35:200/25* | 250/40:500/25* | 400/45:600/30 | 600/45 | |
70 | 200/30:300/25* | 300/40:500/25* | 500/40:600/35 | 600/80 | |
80 | 200/35:300/25* | 350/40:600/25* | 550/55:600/40 | (1) | |
R 90 | 30 | 150/35:200/25* | 200/45:300/25* | 300/45:550/25* | 500/50:600/40 |
40 | 200/35:250/25* | 250/45:500/25* | 350/50:600/25* | 550/50:600/45 | |
50 | 200/40:300/25* | 300/45:550/25* | 500/50:600/35 | 600/55 | |
60 | 200/50:400/25 | 350/50:600/25* | 550/50:600/45 | (1) | |
70 | 300/35:500/25* | 400/50:600/35 | 600/50 | (1) | |
80 | 300/40:600/25* | 500/55:600/40 | 600/80 | (1) | |
R 120 | 30 | 200/45:300/25* | 300/45:550/25* | 450/50:600/25* | 500/60:600/50 |
40 | 200/50:350/25* | 350/50:550/25* | 500/50:600/40 | 600/55 | |
50 | 250/45:450/25* | 450/50:600/25* | 500/55:550/45 | 600/80 | |
60 | 300/50:500/25* | 500/45:600/40 | 550/60:600/60 | (1) | |
70 | 350/50:550/25* | 500/50:550/45 | 600/75 | (1) | |
80 | 400/50:600/25* | 500/55:550/50 | (1) | (1) | |
R 180 | 30 | 300/45:450/25* | 450/50:600/25* | 500/60:600/50 | 600/75 |
40 | 350/50:500/25* | 500/50:600/25* | 600/60 | (1) | |
50 | 450/50:500/25* | 500/60:600/50 | 600/70 | (1) | |
60 | 500/50:600/25* | 550/60:600/55 | (1) | (1) | |
70 | 500/55:600/35 | 600/65 | (1) | (1) | |
80 | 500/60:600/55 | 600/75 | (1) | (1) | |
R 240 | 30 | 450/45:500/25* | 550/55:600/25 | 600/70 | (1) |
40 | 450/50:550/25* | 600/50 | 600/80 | (1) | |
50 | 500/55:600/25* | 600/65 | (1) | (1) | |
60 | 550/55:600/40 | 600/75 | (1) | (1) | |
70 | 600/60 | (1) | (1) | (1) | |
80 | 600/70 | (1) | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
|
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 250/35:300/25* | 500/40:550/25* |
40 | 150/25* | 150/30:200/25* | 300/35:450/25* | 550/30 | |
50 | 150/25* | 200/30:250/25* | 400/40:500/25* | 550/50:600/40 | |
60 | 150/25* | 200/35:300/25* | 450/50:550/25* | (1) | |
70 | 150/25* | 250/40:400/25* | 500/40:600/30 | (1) | |
80 | 150/25* | 300/40:500/25* | 550/50:600/40 | (1) | |
R 60 | 30 | 150/30:200/25* | 200/40:450/25* | 450/50:550/30 | 550/50:600/40 |
40 | 150/35:250/25* | 250/40:500/25* | 500/40:550/35 | 600/60 | |
50 | 200/35:300/25* | 300/45:550/25* | 500/55:550/40 | (1) | |
60 | 200/40:500/25* | 400/40:600/30 | 550/50:600/45 | (1) | |
70 | 200/40:550/25* | 500/40:550/35 | 600/60 | (1) | |
80 | 250/40:600/25* | 500/45:600/35 | (1) | (1) | |
R 90 | 30 | 250/40:450/25* | 300/50:500/25* | 500/55:600/40 | 600/80 |
40 | 200/50:500/25* | 350/50:550/35 | 550/60:600/50 | (1) | |
50 | 250/45:550/25* | 500/45:550/40 | 600/60 | (1) | |
60 | 250/50:550/30 | 500/50:550/45 | 600/80 | (1) | |
70 | 300/50:550/35 | 550/50:600/45 | (1) | (1) | |
80 | 350/50:600/35 | 550/60:600/50 | (1) | (1) | |
R 120 | 30 | 250/50:550/25* | 500/50:550/40 | 550/50 | (1) |
40 | 300/50:600/25* | 500/55:550/45 | 550/60:600/55 | (1) | |
50 | 400/50:550/35 | 500/60:600/45 | 600/80 | (1) | |
60 | 450/50:600/40 | 550/50 | (1) | (1) | |
70 | 500/50:550/45 | 550/60:600/55 | (1) | (1) | |
80 | 550/50:600/45 | 600/70 | (1) | (1) | |
R 180 | 30 | 500/45:550/30 | 550/55 | 600/75 | (1) |
40 | 500/50:600/40 | 550/60 | (1) | (1) | |
50 | 500:60:550/50 | 600/70 | (1) | (1) | |
60 | 550/55 | 600/75 | (1) | (1) | |
70 | 550/60 | (1) | (1) | (1) | |
80 | 600/60 | (1) | (1) | (1) | |
R 240 | 30 | 550/50:600/45 | 600/70 | (1) | (1) |
40 | 550/60:600/55 | 600/75 | (1) | (1) | |
50 | 600/65 | (1) | (1) | (1) | |
60 | 600/70 | (1) | (1) | (1) | |
70 | 600/75 | (1) | (1) | (1) | |
80 | 600/80 | (1) | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
|
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 150/25* | 150/25* |
40 | 150/25* | 150/25* | 150/25* | 150/25* | |
50 | 150/25* | 150/25* | 150/25* | 150/30:200/25* | |
60 | 150/25* | 150/25* | 15025* | 200/30:250/25* | |
70 | 150/25* | 150/25* | 150/30:200/25* | 250/25* | |
80 | 150/25* | 150/25* | 200/30:250/25* | 250/30:300/25* | |
R 60 | 30 | 150/25* | 150/25* | 150/25* | 200/40:300/25* |
40 | 150/25* | 150/25* | 200/30:250/25* | 250/35:350/25* | |
50 | 150/25* | 150/30:200/25* | 200/40:250/25* | 250/40:350/25* | |
60 | 150/25* | 150/40:250/25* | 250/35:300/25* | 300/40:600/25* | |
70 | 150/25* | 200/35:250/25* | 250/40:400/25* | 350/40:450/35 | |
80 | 150/30:200/25* | 200/40:300/25* | 300/40:550/25* | 350/45:450/40 | |
R 90 | 30 | 150/25* | 200/25* | 200/40:250/25* | 250/45:600/25* |
40 | 150/25* | 200/35:250/25* | 250/35:350/25* | 300/45:600/30 | |
50 | 150/35:200/25* | 200/40:250/25* | 250/45 400/25* | 350/45:600/35 | |
60 | 150/40:250/25* | 250/55:300/25* | 300/45:550/25* | 400/50:600/40 | |
70 | 200/35:250/25* | 300/35:350/25* | 350/45:600/35 | 550/50:600/45 | |
80 | 200/40:250/25* | 300/40:500/25 | 350/50:600/40 | 550/65:600/55 | |
R 120 | 30 | 150/40:200/25* | 200/45:250/25* | 250/40:400/25* | 400/40:600/25* |
40 | 200/30:250/25* | 250/25* | 300/45:400/25* | 400/50:600/30 | |
50 | 200/40:250/25* | 250/35:300/25* | 350/40:550/25* | 550/45:600/40 | |
60 | 200/45:250/25* | 250/45:400/25* | 400/50:600/25* | 550/60:600/50 | |
70 | 250/25* | 350/35:450/25* | 550/40:600/35 | 600/70 | |
80 | 250/35:300/25* | 350/40:550/25* | 550/50:600/45 | (1) | |
R 180 | 30 | 200/50:250/25* | 300/25* | 350/45:450/25* | 500/50:600/45 |
40 | 250/25* | 300/45:350/25* | 450/45:550/25* | 550/60:600/55 | |
50 | 250/30:300/25* | 350/40:450/25* | 450/50:600/40 | 600/70 | |
60 | 250/40:350/25* | 350/50:500/25* | 550/55:600/50 | 600/80 | |
70 | 300/45:400/25* | 450/45:600/35 | 550/70:600/65 | (1) | |
80 | 350/40:450/25* | 550/50:600/40 | 600/75 | (1) | |
R 240 | 30 | 250/25* | 350/40:400/25* | 500/40:600/25* | 550/70:600/60 |
40 | 250/40:350/25* | 400/50:450/25* | 500/60:600/40 | 600/75 | |
50 | 350/30:400/25* | 450/45:550/25* | 550/55:600/50 | (1) | |
60 | 350/45:450/25* | 500/50:600/35 | 600/70 | (1) | |
70 | 400/50:500/25* | 500/60:600/45 | (1) | (1) | |
80 | 450/45:550/25* | 550/60:600/50 | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
|
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 150/25* | 200/30:300/25 |
40 | 150/25* | 150/25* | 150/25* | 250/30:450/25* | |
50 | 150/25* | 150/25* | 200/25* | 300/35:500/25* | |
60 | 150/25* | 150/25* | 200/30:250/25* | 400/40:550/25* | |
70 | 150/25* | 150/25* | 250/35:300/25* | 500/35:600/30 | |
80 | 150/25* | 150/30:250/25* | 300/35:500/25* | 500/60:600/35 | |
R 60 | 30 | 150/25* | 150/30:200/25* | 200/40:400/25* | 300/50:600/30 |
40 | 150/25* | 150/40:250/25* | 250/40:500/25* | 400/50:600/35 | |
50 | 150/25* | 200/35:400/25* | 300/40:600/25* | 500/45:600/40 | |
60 | 150/30:200/25* | 200/40:450/25* | 400/40:600/30 | 550/40:600/40 | |
70 | 150/35:200/25* | 240/40:550/25* | 450/45:500/35 | 600/60 | |
80 | 200/30:250/25 | 300/40:550/25 | 500/50:600/40 | 600/80 | |
R 90 | 30 | 200/25* | 200/40:300/25* | 250/40:550/25* | 500/50:600/45 |
40 | 200/30:250/25* | 200/50:400/25* | 300/50:600/35 | 500/60:600/50 | |
50 | 200/35:300/25* | 250/50:550/25* | 400/50:600/40 | 600/55 | |
60 | 200/40:400/25 | 300/45:600/25* | 500/50:600/45 | 600/70 | |
70 | 200/45:450/25* | 300/50:600/35 | 550/55:600/50 | (1) | |
80 | 200/50:500/25* | 400/50:600/35 | 600/55 | (1) | |
R 120 | 30 | 200/40:250/25 | 250/50:400/25* | 450/45:600/30 | 600/60 |
40 | 200/45:300/25* | 300/40:500/25* | 500/50:600/35 | (1) | |
50 | 250/40:400/25* | 400/40:550/25* | 550/50:600/45 | (1) | |
60 | 250/50:450/25* | 400/50:500/35 | 600/55 | (1) | |
70 | 300/40:500/25* | 500/45:600/35 | (1) | (1) | |
80 | 300/50:550/25* | 500/60:600/40 | (1) | (1) | |
R 180 | 30 | 300/35:400/25* | 450/50:550/25* | 500/60:600/45 | (1) |
40 | 300/40:450/25* | 500/40:600/30 | 550/65:600/60 | (1) | |
50 | 400/40:500/25* | 500/45:600/35 | 600/75 | (1) | |
60 | 400/45:550/25* | 500/55:600/45 | (1) | (1) | |
70 | 400/50:600/30 | 500/65:600/50 | (1) | (1) | |
80 | 500/45:600/35 | 600/70 | (1) | (1) | |
R 240 | 30 | 400/45:500/25* | 500/40:600/30 | 600/60 | (1) |
40 | 450/45:550/25* | 500/55:600/40 | 600/80 | (1) | |
50 | 450/50:600/25* | 500/65:600/45 | (1) | (1) | |
60 | 500/45:600/35 | 550/70:600/55 | (1) | (1) | |
70 | 500/50:600/40 | 600/75 | (1) | (1) | |
80 | 500/60:600/45 | (1) | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
|
Standard fire resistance | λ | Minimum dimensions (mm) Column width bmin/axis distance a | |||
Column exposed on more than one side | |||||
n = 0,15 | n = 0,3 | n = 0,5 | n = 0,7 | ||
1 | 2 | 3 | 4 | 5 | 6 |
R 30 | 30 | 150/25* | 150/25* | 200/30:300/25* | 500/30:550/25 |
40 | 150/25* | 150/25* | 250/30:450/25* | 500/40:600/30 | |
50 | 150/25* | 150/30:200/25* | 300/35:500/25* | 550/35 | |
60 | 150/25* | 200/30:250/25* | 350/40:500/25* | 550/50 | |
70 | 150/25* | 200/30:300/25* | 450/50:550/25* | (1) | |
80 | 150/25* | 250/30:350/25* | 500/35:600/30 | (1) | |
R 60 | 30 | 150/25* | 200/35:450/25* | 350/40:600/30 | 550/45:600/40 |
40 | 150/30:200/25* | 200/40:500/25* | 450/50:500/35 | 600/60 | |
50 | 150/35:250:25* | 250/40:550/25* | 500/40:600/35 | 600/80 | |
60 | 200/30:350/25* | 300/40:600/25* | 500/50:600/40 | (1) | |
70 | 250/30:450/25* | 350/40:600/30 | 550/50:600/45 | (1) | |
80 | 250/55:500/25* | 450/40:500/35 | 600/70 | (1) | |
R 90 | 30 | 200/35:300/25* | 250/50:550/25* | 500/50:600/40 | 600/70 |
40 | 200/40:450/25* | 300/50:600/30 | 500/55:600/45 | (1) | |
50 | 200/45:500:25* | 350/50:600/35 | 550/50 | (1) | |
60 | 200/50:550/25* | 450/50:600/40 | 600/60 | (1) | |
70 | 250/45:600/30 | 500/50:600/45 | 600/80 | (1) | |
80 | 250/50:500/35 | 500/55:600/45 | (1) | (1) | |
R 120 | 30 | 200/50:450/25* | 450/45:600/25* | 550/55:600/50 | (1) |
40 | 250/50:500/25* | 500/40:600/30 | 600/65 | (1) | |
50 | 300/40:550/25* | 500/50:600/35 | (1) | (1) | |
60 | 350/45:550/25* | 500/60:600/40 | (1) | (1) | |
70 | 450/40:600/30 | 550/60:600/50 | (1) | (1) | |
80 | 450/45:600/30 | 600/65 | (1) | (1) | |
R 180 | 30 | 350/45:550/25* | 500/45:600/40 | 600/80 | (1) |
40 | 450/45:600/30 | 500/60:600/45 | (1) | (1) | |
50 | 450/50:600/35 | 500/70:600/55 | (1) | (1) | |
60 | 500/45:600/40 | 550/70:600/65 | (1) | (1) | |
70 | 500/50:600/40 | 600/75 | (1) | (1) | |
80 | 500/55:600/45 | (1) | (1) | (1) | |
R 240 | 30 | 500/40:600/35 | 550/55:600/50 | (1) | (1) |
40 | 500/50:600/40 | 550/65:600/55 | (1) | (1) | |
50 | 500/55:600/45 | 600/70 | (1) | (1) | |
60 | 500/60:600/45 | (1) | (1) | (1) | |
70 | 500/70:600/50 | (1) | (1) | (1) | |
80 | 550/60:600/55 | (1) | (1) | (1) | |
* Normally the cover required by EN 1992-1-1 will control. | |||||
|
(Informative)
Note: Shear failures due to fire are very uncommon. However, the calculation methods given in this Annex are not fully verified.
In the absence of more accurate information concerning the reduction of the tensile strength of concrete, the values of kct(θ) given Figure 3.2 may be applied.
Figure D.1: Shear cracks intersect links at various levels above bending reinforcement.
Figure D.2: The reference temperature θp should be evaluated at points along the line ‘a -a’ for the calculation of the shear resistance. The effective tension area may be obtained from
EN 1992-1-1
(SLS of cracking).
Figure D.3: The reference temperature θp should be evaluated at points along the line ‘a -a’ for the calculation of torsion resistance.
(Informative)
Note: The method can be applied for continuous beams or slabs where moment redistribution is higher than 15% if sufficient rotational capacity is provided at the supports for the required fire exposure conditions.
The minimum cross-section dimensions (bmin, bw, hs) given in Tables 5.5 to 5.11 should not be reduced.
This method uses strength reduction factors based on Figure 5.1
MEd,fi ≤ MRd,fi (E.1)
MEd,fi = WEd,fi leff2 / 8 (E.2)
Where
WEd,fi | is the uniformly distributed load (kN/m) under fire conditions |
leff | is the effective length of beam or slab |
MRd,fi = (γ / γs,fi) × Ks(θ) × MEd (As,prov / As,req) (E.3)
where:
γs | is the partial material factor for steel used in EN 1992-1-1 7 |
γs,fi | is the partial material factor for steel under fire conditions |
Ks(θ) | is a strength reduction factor of the steel for the given temperature θ under the required fire resistance. θ may be taken from Annex A for the chosen axis distance |
MEd | is the applied moment for cold design to EN 1992-1-1 |
As,prov | is the area of tensile steel provided |
As,req | is the area of tensile steel required for the design at ambient temperature to EN 1992-1-1 |
As,prov / As,req | should not be taken as greater than 1,3. |
MRd,fi = (γs / γs,fi) MEd (As,Prov / As,req) (d-a)/d (E.4)
where
γs, γs,fi, MEd, As,prov, As,req are as defined E.2
a | is the required average bottom axis distance given in Table 5.5, Column 5 for beams and Table 5.8, Column 3 for slabs |
d | is the effective depth of section |
As,prov/As,req | should not be taken as greater than 1,3. |
Figure E. 1: Positioning the free bending moment diagram MEd,fi to establish equilibrium.
For higher temperatures MRd,fi should be reduced by Ks(θcr) or Kp(θcr) according to Figure 5.1.
lbd,fi = (γs / γs,fi)(γc,fi / γc) · lbd (E.5)
where lbd is given in Section 8 of EN 1992-1-1.
The length of bar provided should extend beyond the support to the relevant contra-flexure point as calculated in E.3 (3) plus a distance equal to lbd,fi.